Performance Analysis of Industrial Ventilation Systems: A Case Study of Exhaust Fan and Roof Cooling Fan Installations in a Textile Manufacturing Area

https://doi.org/10.47194/orics.v6i4.438

Authors

Keywords:

Exhaust fan, industrial ventilation, energy performance, temperature and humidity, textile industry

Abstract

This study presents a performance analysis of industrial ventilation systems using exhaust fans and roof cooling fans in a textile manufacturing environment. The research was conducted as a case study in the Preparation and Processing areas of a textile factory located in Cimahi, West Java, Indonesia, under actual operating conditions. Air temperature and relative humidity (RH) were measured and compared with recommended textile industry standards (20–30°C and RH 55–75%). Two mechanical ventilation alternatives were evaluated: an exhaust fan system (1.46 × 1.46 m) and a roof cooling fan system (1.82 × 1.45 m). The results show that areas equipped with exhaust fans exhibited lower indoor temperatures by approximately 2–3°C and more stable RH levels (50–52%) compared to areas without mechanical ventilation, where temperatures reached up to 42°C and RH dropped to 25–30%. Both systems required 0.75 kW per unit, with monthly operating costs ranging from IDR 7–10 million. Volumetric efficiency analysis indicates that exhaust fans achieved 60,000 m³/kWh, while roof cooling fans produced 46,667 m³/kWh, indicating a 28% difference in airflow efficiency. These findings provide empirical evidence on the thermal and energy performance characteristics of industrial ventilation systems in textile production areas.

References

Amien, F. & Kemenkes Makassar, P. (2025). Exposure to Particulate Matter (PM 10 and PM 2.5) in the Work Environment at the PT Vale Sorowako Smelter Plant, East Luwu. Sulolipu Journal, 25(2), 301–308.

Anders, B. D., & Santaram, V. (2021). Design of a Ventilation System to Improve IAQ and Thermal Comfort in a Textile Factory. Indoor Environmental Quality Performance Approaches, 1–11. www.ashrae.org

Anh, A. T. H. T., Cuong, T. H., & Khoi, T. Van. (2025). Cascaded H-bridge 7-level inverter application for air exhaust fan drive control of Thu Thiem road tunnel. Bulletin of Electrical Engineering and Informatics, 14(1), 108–117. https://doi.org/10.11591/eei.v14i1.8490

Ashrae Research. (2021). 2021 ASHRAE handbook. Fundamentals. ASHRAE.

Elhadary, M. I., Alzahrani, A. M., Aly, R. M. H., & Elboshy, B. (2021). A comparative study for forced ventilation systems in industrial buildings to improve the workers’ thermal comfort. Sustainability, 13(18), 10267. https://doi.org/10.3390/su131810267

Fallah, B. W., & Mashuri, P. (2025). Critical Control Point Analysis of Physical Environment on Work Stress in Textile Industry. Metode Jurnal Teknik Industri, 11(2), 2025.

Fawwaz, R. M., & Tjahjanti, H. P. (2025). Air Circulation Improvement through Exhaust and Fan Installation. In Procedia of Engineering and Life Science (Vol. 8, Issue 1).

Ikpe, A.E. (2024). The role of mechanical ventilation systems and their applications in contemporary engineering practices. Optimality, Vol. 1, No. 2.

Izadyar, N., & Miller, W. (2022). Ventilation strategies and design impacts on indoor airborne transmission: A review. Building and Environment, 218, 109158. https://doi.org/10.1016/j.buildenv.2022.109158

Verma, A., & Gupta, S. (2025). Numerical simulation of exhaust position for optimized ventilation in a textile manufacturing plant: A CFD study. International Journal of Engineering Applied Sciences and Technology, 9(10), 30–41.

Wang, Y., Cao, Y., & Meng, X. (2019). Energy efficiency of industrial buildings. In Indoor and Built Environment (Vol. 28, Issue 3, pp. 293–297). SAGE Publications Ltd.

Yulindra, M. (2011). The Relationship Between Byssinosis Incidence and the Level of Cotton Dust Exposure in Textile Workers at PT ASATEX Yogyakarta.

Published

2025-12-31

How to Cite

noviandani, pradika, Latipah, Y., Sari, M. H. R. S. R., & Suryaman. (2025). Performance Analysis of Industrial Ventilation Systems: A Case Study of Exhaust Fan and Roof Cooling Fan Installations in a Textile Manufacturing Area. Operations Research: International Conference Series, 6(4), 163–168. https://doi.org/10.47194/orics.v6i4.438